  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Public",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "We strongly recommend the following industry cybersecurity best practices.\n\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the “Program” mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\n\nFor more information refer to the Schneider Electric [Recommended Cybersecurity Best Practices](https://www.se.com/us/en/download/document/7EN52-0390/) document.",
        "title": "General Security Recommendations"
      },
      {
        "category": "general",
        "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\n\nFor further information related to cybersecurity in Schneider Electric's products, visit the company's cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
        "title": "For More Information"
      },
      {
        "category": "legal_disclaimer",
        "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND.  SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
        "title": "LEGAL DISCLAIMER"
      },
      {
        "category": "general",
        "text": "Schneider's purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and\r\nsustainability for all. We call this Life Is On.\n\nOur mission is to be the trusted partner in Sustainability and Efficiency.\n\nWe are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart\r\nindustries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep\r\ndomain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,\r\nsoftware and services, delivering digital twins to enable profitable growth for our customers.\n\nWe are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries\r\nto ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our\r\nmeaningful purpose of a sustainable future for all. \n\n www.se.com",
        "title": "About Schneider Electric"
      },
      {
        "category": "summary",
        "text": "Schneider Electric is aware of multiple vulnerabilities in its EcoStruxure™ Control Expert ,\r\nEcoStruxure™ Process Expert and Modicon M340, M580 PLCs (Programmable Logic\r\nControllers).\r\nModicon PLCs control and monitor industrial operations. EcoStruxure™ Control Expert is the\r\ncommon programming, debugging and operating software for Modicon PLCs. EcoStruxure™\r\nProcess Expert DCS is a single automation system to engineer, operate, and maintain an entire\r\nplant Infrastructure.\r\nFailure to apply the remediations provided below may risk unauthorized access to your PLC,\r\nwhich could result in the possibility of denial of service and loss of confidentiality, integrity of the\r\ncontroller.\r\n\r\nNote regarding vulnerability details: The severity of vulnerabilities was calculated using the\r\nCVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and\r\nEnvironmental metrics. Schneider Electric recommends that customers score the CVSS\r\nEnvironmental metrics, which are specific to end-user organizations, and consider factors such\r\nas the presence of mitigations in that environment. Environmental metrics may refine the\r\nrelative severity posed by the vulnerabilities described in this document within a customer’s \renvironment",
        "title": "Overview"
      },
      {
        "category": "other",
        "text": "The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 ([CVSS v4.0](https://www.first.org/cvss/calculator/4.0)). CVSS v3.1 \nwill be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without \nincorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as \nthe presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer's environment."
      },
      {
        "category": "other",
        "text": "Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric's [Customer Care Center](https://www.se.com/us/en/work/support/contacts.jsp) if you need assistance removing a patch. "
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "cpcert@se.com",
      "name": "Schneider Electric CPCERT",
      "namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
    },
    "references": [
      {
        "category": "self",
        "summary": "EcoStruxure™ Control Expert, EcoStruxure™ Process Expert and Modicon M340, M580 and M580 Safety PLCs - SEVD-2024-044-01 PDF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2024-044-01&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2024-044-01.pdf"
      },
      {
        "category": "self",
        "summary": "EcoStruxure™ Control Expert, EcoStruxure™ Process Expert and Modicon M340, M580 and M580 Safety PLCs - SEVD-2024-044-01 CSAF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2024-044-01&p_enDocType=Security+and+Safety+Notice&p_File_Name=sevd-2024-044-01.json"
      },
      {
        "category": "external",
        "summary": "Recommended Cybersecurity Best Practices",
        "url": "https://www.se.com/ww/en/download/document/7EN52-0390/"
      }
    ],
    "title": "EcoStruxure™ Control Expert, EcoStruxure™ Process Expert and Modicon M340, M580 and M580 Safety PLCs",
    "tracking": {
      "current_release_date": "2026-04-14T07:00:00.000Z",
      "generator": {
        "date": "2026-04-13T13:08:28.226Z",
        "engine": {
          "name": "Schneider Electric CSAF Generator",
          "version": "1.2"
        }
      },
      "id": "SEVD-2024-044-01",
      "initial_release_date": "2024-02-13T12:41:43.000Z",
      "revision_history": [
        {
          "date": "2024-02-13T12:41:43.000Z",
          "number": "1.0.0",
          "summary": "Original Release"
        },
        {
          "date": "2024-07-09T00:00:00.000Z",
          "number": "2.0.0",
          "summary": "Modicon MC80 and Momentum M1E PLCs have been identified as impacted by the CVE-2023-6408. Mitigations are now available"
        },
        {
          "date": "2024-08-13T00:00:00.000Z",
          "number": "3.0.0",
          "summary": "A remediation is available for the Modicon M580 CPU Safety (page 3)."
        },
        {
          "date": "2026-04-14T07:00:00.000Z",
          "number": "4.0.0",
          "summary": "Remediation is available for Modicon Momentum controller "
        }
      ],
      "status": "final",
      "version": "4.0.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:generic/<SV3.60",
                "product": {
                  "name": "Modicon M340 CPU (part numbers BMXP34*) Versions prior to sv3.60",
                  "product_id": "1"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M340 CPU (part numbers BMXP34*)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:generic/<SV4.20",
                "product": {
                  "name": "Modicon M580 CPU (part numbers BMEP* and BMEH* excluding M580 CPU Safety) Versions prior to sv4.20",
                  "product_id": "2"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU (part numbers BMEP* and BMEH* excluding M580 CPU Safety)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:generic/<SV4.21",
                "product": {
                  "name": "Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) Versions prior to SV4.21",
                  "product_id": "3",
                  "product_identification_helper": {
                    "model_numbers": [
                      "BMEP58*S",
                      "BMEH58*S"
                    ]
                  }
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU Safety"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:generic/SV4.21",
                "product": {
                  "name": "Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) Version SV4.21",
                  "product_id": "12",
                  "product_identification_helper": {
                    "model_numbers": [
                      "BMEP58*S",
                      "BMEH58*S"
                    ]
                  }
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU Safety"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:intdot/<16.0",
                "product": {
                  "name": "EcoStruxure™ Control Expert Versions prior to v16.0",
                  "product_id": "4"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure™ Control Expert"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:generic/<2023",
                "product": {
                  "name": "EcoStruxure™ Process Expert Versions prior to v2023",
                  "product_id": "5"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure™ Process Expert"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "SV3.60",
                "product": {
                  "name": "Modicon M340 CPU (part numbers BMXP34*) SV3.60",
                  "product_id": "6"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M340 CPU (part numbers BMXP34*)"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "SV4.20",
                "product": {
                  "name": "Modicon M580 CPU (part numbers BMEP* and BMEH*, excluding M580 CPU Safety)  SV4.20",
                  "product_id": "7"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU (part numbers BMEP* and BMEH*, excluding M580 CPU Safety)"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "16.0",
                "product": {
                  "name": "EcoStruxure™ Control Expert Version 16.0",
                  "product_id": "8"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure™ Control Expert"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "15.3 HF008",
                "product": {
                  "name": "EcoStruxure™ Process Expert Version 15.3 HF008",
                  "product_id": "9"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure™ Process Expert"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Modicon MC80 (part numbers BMKC80) All Versions",
                  "product_id": "10"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon MC80 (part numbers BMKC80)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:generic/<SV2.90",
                "product": {
                  "name": "Modicon Momentum Unity M1E Processor Firmware Versions prior to SV2.90",
                  "product_id": "11"
                }
              },
              {
                "category": "product_version",
                "name": "SV2.90",
                "product": {
                  "name": "Modicon Momentum Unity M1E  Processor Firmware Version SV2.90",
                  "product_id": "13"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon Momentum Unity M1E Processor Firmware"
          },
          {
            "category": "product_name",
            "name": "Modicon Momentum Unity M1E Processor Controller",
            "product": {
              "name": "Modicon Momentum Unity M1E Processor Controller",
              "product_id": "14",
              "product_identification_helper": {
                "model_numbers": [
                  "171CBU*"
                ]
              }
            }
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      }
    ],
    "relationships": [
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Modicon Momentum Unity M1E Processor Firmware Versions prior to SV2.90 installed on Modicon Momentum Unity M1E Processor Controller",
          "product_id": "15",
          "product_identification_helper": {
            "model_numbers": [
              "171CBU*"
            ]
          }
        },
        "product_reference": "11",
        "relates_to_product_reference": "14"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Modicon Momentum Unity M1E Processor Firmware Version SV2.90 installed on Modicon Momentum Unity M1E Processor Controller",
          "product_id": "16",
          "product_identification_helper": {
            "model_numbers": [
              "171CBU*"
            ]
          }
        },
        "product_reference": "13",
        "relates_to_product_reference": "14"
      }
    ]
  },
  "vulnerabilities": [
    {
      "acknowledgments": [
        {
          "names": [
            "Gao Jian"
          ]
        }
      ],
      "cve": "CVE-2023-6408",
      "cwe": {
        "id": "CWE-924",
        "name": "Improper Enforcement of Message Integrity During Transmission in a Communication Channel"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-924: Improper Enforcement of Message Integrity During Transmission in a\r\nCommunication Channel vulnerability exists that could cause a denial of service and loss of\r\nconfidentiality, integrity of controllers when conducting a Man in the Middle attack.",
          "title": "CVE Description"
        },
        {
          "category": "details",
          "text": "CVSS v4.0 Base Score 9.2 | Critical | [CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N](https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N)",
          "title": "CVSS v4.0 Score"
        }
      ],
      "product_status": {
        "fixed": [
          "6",
          "7",
          "8",
          "9",
          "12",
          "16"
        ],
        "known_affected": [
          "1",
          "2",
          "3",
          "4",
          "5",
          "10",
          "15"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "SV3.60 of Modicon M340 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/1468-\r\nmodicon-m340",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/1468-modicon-m340"
        },
        {
          "category": "vendor_fix",
          "details": "SV4.20 of Modicon M580 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/62098-\r\nmodicon-m580-epac/ - software-and-firmware",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/62098-%20modicon-m580-epac/%20-%20software-and-firmware"
        },
        {
          "category": "vendor_fix",
          "details": "Version 16.0 of EcoStruxure Control Expert includes a fix\r\nfor these vulnerabilities and is available for download\r\nhere:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/\r\nReboot the computer after installation is completed",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/in/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "vendor_fix",
          "details": "Version 15.3 HF008 of EcoStruxure Control Expert\r\nincludes the fix for these vulnerabilities and are available\r\nfor download here:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware SV4.21 includes a fix for this vulnerability and \r\nis available for download here: https://www.se.com/ww/en/product-range/62098-modicon-m580-pac-controller/#software-andfirmware\r\nImportant: customer needs to use version of \r\nEcoStruxure™ Control Expert v16.0 HF001 minimum to \r\nconnect with the latest version of M580 CPU Safety. The \r\nsoftware is available for download here:\r\nhttps://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/#software-andfirmware",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/62098-modicon-m580-pac-controller/#software-andfirmware"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n• Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n• Configure the Access Control List following the recommendations of the\r\nuser manuals: “Modicon M340 for Ethernet Communications Modules\r\nand Processors User Manual” in chapter “Messaging Configuration\r\nParameters”:\r\nhttps://www.se.com/ww/en/download/document/31007131K01000/\r\n• Setup a secure communication according to the following guideline\r\n“Modicon Controllers Platform Cyber Security Reference Manual,” in\r\nchapter “Setup secured communications”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 & M580 architectures.\r\nFor more details refer to the chapter “How to protect M580 and M340\r\narchitectures with EAGLE40 using VPN”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Ensure the M340 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline “Modicon Controllers Platform Cyber Security\r\nReference Manual”, “CPU Memory Protection section”:\r\n• https://www.se.com/ww/en/download/document/EIO0000001999/",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/31007131K01000/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n• Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n• Configure the Access Control List following the recommendations of the\r\nuser manuals: “Modicon M580, Hardware, Reference Manual”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\nSetup a secure communication according to the following guideline\r\n“Modicon Controllers Platform Cyber Security Reference Manual,” in\r\nchapter “Setup secured communications”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline “Modicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration\r\nGuide” in the chapter “Configuring IPSEC communications”:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n• Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter “Configuring the\r\nBMENUA0100 Cybersecurity Settings”:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n• Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 & M580 architectures.\r\nFor more details refer to the chapter “How to protect M580 and M340\r\narchitectures with EAGLE40 using VPN”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline “Modicon Controllers Platform Cyber Security\r\nReference Manual”, “CPU Memory Protection section”:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580 Hot\r\nStandby CPUs. In such cases, use IPsec encrypted communication.",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation then they are encouraged to immediately apply the following mitigations to reduce the risk of exploit:\r\n• Setup an application password in the project properties\r\n• Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n• Configure the Access Control List following the recommendations of the\r\nuser manuals: “Modicon M580, Hardware, Reference Manual”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\n• Setup a secure communication according to the following guideline\r\n“Modicon Controllers Platform Cyber Security Reference Manual,” in\r\nchapter “Setup secured communications”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline “Modicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration Guide” in the chapter “Configuring IPSEC communications”:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n• Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter “Configuring the\r\nBMENUA0100 Cybersecurity Settings”:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n• Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 & M580 architectures.\r\nFor more details refer to the chapter “How to protect M580 and M340\r\narchitectures with EAGLE40 using VPN”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline “Modicon Controllers Platform Cyber Security\r\nReference Manual”, “CPU Memory Protection section”:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580\r\nHot Standby CPUs. In such cases, use IPsec encrypted\r\ncommunication.\r\n• To further reduce the attack surface on Modicon M580 CPU\r\nSafety:\r\nEnsure the CPU is running in Safety mode and maintenance input is\r\nconfigured to maintain this Safety mode during operation – refer to\r\nthe document Modicon M580 - Safety System Planning Guide - in\r\nthe chapter “Operating Mode Transitions”:\r\nhttps://www.se.com/ww/en/download/document/QGH60283/ ",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "Enable encryption on application project and store application files in\r\nsecure location with restricted access only for legitimate users.\r\n• Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n• Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        },
        {
          "category": "mitigation",
          "details": "EcoStruxure Process Expert manages application files within its\r\ndatabase in secure way. Do not export & store them outside the\r\napplication.\r\n• Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n• Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties• Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP• Configure the Access Control List following the recommendations of the user manuals:• “Modicon MC80 Programmable Logic Controller (PLC) manual” in the chapter “Access Control List (ACL)”:https://www.se.com/ww/en/download/document/EIO0000002071/Setup a secure communication according to the following guideline “Modicon Controller Systems Cybersecurity, User Guide” in chapter “Set Up Encrypted Communication”:",
          "product_ids": [
            "10"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001999/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties• Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP• Setup a secure communication according to the following guideline “Modicon Controller Systems Cybersecurity, User Guide” in chapter “Set Up Encrypted Communication”:",
          "product_ids": [
            "15"
          ],
          "url": "https://www.se.com/ww/en/download/document/EIO0000001999/"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware SV2.90 includes a fix for this vulnerability and is \navailable for download here: \n \nhttps://www.se.com/ww/en/product-range/535-modicon-momentum/ \n \nImportant: customer needs to use version of EcoStruxure™ \nControl Expert v16.2 HF003 minimum to connect with the latest \nversion of Modicon Momentum. The software is available for \ndownload here: \n \nhttps://www.se.com/ww/en/product-range/548-ecostruxure\ncontrol-expert-unity-pro/#software-and-firmware",
          "product_ids": [
            "15"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/ww/en/product-range/535-modicon-momentum/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 8.1,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1",
            "2",
            "3",
            "4",
            "5",
            "10",
            "15"
          ]
        }
      ],
      "title": "CVE-2023-6408"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Jianshuang Ding"
          ]
        }
      ],
      "cve": "CVE-2023-6409",
      "cwe": {
        "id": "CWE-798",
        "name": "Use of Hard-coded Credentials"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-798: Use of Hard-coded Credentials vulnerability exists that could cause unauthorized\r\naccess to a project file protected with application password when opening the file with\r\nEcoStruxure Control Expert.",
          "title": "CVE Description"
        },
        {
          "category": "details",
          "text": "CVSS v4.0 Base Score 8.5 | High | [CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N](https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N)",
          "title": "CVSS v4.0 Score"
        }
      ],
      "product_status": {
        "fixed": [
          "8",
          "9"
        ],
        "known_affected": [
          "4",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "SV3.60 of Modicon M340 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/1468-\r\nmodicon-m340",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/1468-modicon-m340"
        },
        {
          "category": "vendor_fix",
          "details": "SV4.20 of Modicon M580 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/62098-\r\nmodicon-m580-epac/ - software-and-firmware",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/62098-%20modicon-m580-epac/%20-%20software-and-firmware"
        },
        {
          "category": "vendor_fix",
          "details": "Version 16.0 of EcoStruxure Control Expert includes a fix\r\nfor these vulnerabilities and is available for download\r\nhere:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/\r\nReboot the computer after installation is completed",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/in/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "vendor_fix",
          "details": "Version 15.3 HF008 of EcoStruxure Control Expert\r\nincludes the fix for these vulnerabilities and are available\r\nfor download here:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n• Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n• Configure the Access Control List following the recommendations of the\r\nuser manuals: “Modicon M340 for Ethernet Communications Modules\r\nand Processors User Manual” in chapter “Messaging Configuration\r\nParameters”:\r\nhttps://www.se.com/ww/en/download/document/31007131K01000/\r\n• Setup a secure communication according to the following guideline\r\n“Modicon Controllers Platform Cyber Security Reference Manual,” in\r\nchapter “Setup secured communications”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 & M580 architectures.\r\nFor more details refer to the chapter “How to protect M580 and M340\r\narchitectures with EAGLE40 using VPN”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Ensure the M340 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline “Modicon Controllers Platform Cyber Security\r\nReference Manual”, “CPU Memory Protection section”:\r\n• https://www.se.com/ww/en/download/document/EIO0000001999/",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/31007131K01000/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n• Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n• Configure the Access Control List following the recommendations of the\r\nuser manuals: “Modicon M580, Hardware, Reference Manual”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\nSetup a secure communication according to the following guideline\r\n“Modicon Controllers Platform Cyber Security Reference Manual,” in\r\nchapter “Setup secured communications”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline “Modicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration\r\nGuide” in the chapter “Configuring IPSEC communications”:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n• Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter “Configuring the\r\nBMENUA0100 Cybersecurity Settings”:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n• Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 & M580 architectures.\r\nFor more details refer to the chapter “How to protect M580 and M340\r\narchitectures with EAGLE40 using VPN”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline “Modicon Controllers Platform Cyber Security\r\nReference Manual”, “CPU Memory Protection section”:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580 Hot\r\nStandby CPUs. In such cases, use IPsec encrypted communication.",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "Schneider Electric is establishing a remediation plan for all future versions\r\nof EcoStruxure™ Process Expert that will include a fix for this vulnerability.\r\nWe will update this document when the remediation is available. Until then,\r\ncustomers should immediately apply the following mitigations to reduce the\r\nrisk of exploit:\r\n• Setup an application password in the project properties\r\n• Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n• Configure the Access Control List following the recommendations of the\r\nuser manuals: “Modicon M580, Hardware, Reference Manual”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\n• Setup a secure communication according to the following guideline\r\n“Modicon Controllers Platform Cyber Security Reference Manual,” in\r\nchapter “Setup secured communications”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline “Modicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration Guide” in the chapter “Configuring IPSEC communications”:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n• Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter “Configuring the\r\nBMENUA0100 Cybersecurity Settings”:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n• Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 & M580 architectures.\r\nFor more details refer to the chapter “How to protect M580 and M340\r\narchitectures with EAGLE40 using VPN”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline “Modicon Controllers Platform Cyber Security\r\nReference Manual”, “CPU Memory Protection section”:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580\r\nHot Standby CPUs. In such cases, use IPsec encrypted\r\ncommunication.\r\n• To further reduce the attack surface on Modicon M580 CPU\r\nSafety:\r\nEnsure the CPU is running in Safety mode and maintenance input is\r\nconfigured to maintain this Safety mode during operation – refer to\r\nthe document Modicon M580 - Safety System Planning Guide - in\r\nthe chapter “Operating Mode Transitions”:\r\nhttps://www.se.com/ww/en/download/document/QGH60283/ ",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "Enable encryption on application project and store application files in\r\nsecure location with restricted access only for legitimate users.\r\n• Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n• Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        },
        {
          "category": "mitigation",
          "details": "EcoStruxure Process Expert manages application files within its\r\ndatabase in secure way. Do not export & store them outside the\r\napplication.\r\n• Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n• Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "NONE",
            "baseScore": 7.7,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N",
            "version": "3.1"
          },
          "products": [
            "4",
            "5"
          ]
        }
      ],
      "title": "CVE-2023-6409"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Kaikai Yang"
          ]
        }
      ],
      "cve": "CVE-2023-27975",
      "cwe": {
        "id": "CWE-522",
        "name": "Insufficiently Protected Credentials"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-522: Insufficiently Protected Credentials vulnerability exists that could cause\r\nunauthorized access to the project file in EcoStruxure™ Control Expert when a local user\r\ntampers with the memory of the engineering workstation.",
          "title": "CVE Description"
        },
        {
          "category": "details",
          "text": "CVSS v4.0 Base Score 7.2 | High | [CVSS:4.0/AV:L/AC:L/AT:P/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N](https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:L/AC:L/AT:P/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N)",
          "title": "CVSS v4.0 Score"
        }
      ],
      "product_status": {
        "fixed": [
          "8",
          "9"
        ],
        "known_affected": [
          "4",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "SV3.60 of Modicon M340 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/1468-\r\nmodicon-m340",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/1468-modicon-m340"
        },
        {
          "category": "vendor_fix",
          "details": "SV4.20 of Modicon M580 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/62098-\r\nmodicon-m580-epac/ - software-and-firmware",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/62098-%20modicon-m580-epac/%20-%20software-and-firmware"
        },
        {
          "category": "vendor_fix",
          "details": "Version 16.0 of EcoStruxure Control Expert includes a fix\r\nfor these vulnerabilities and is available for download\r\nhere:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/\r\nReboot the computer after installation is completed",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/in/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "vendor_fix",
          "details": "Version 15.3 HF008 of EcoStruxure Control Expert\r\nincludes the fix for these vulnerabilities and are available\r\nfor download here:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n• Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n• Configure the Access Control List following the recommendations of the\r\nuser manuals: “Modicon M340 for Ethernet Communications Modules\r\nand Processors User Manual” in chapter “Messaging Configuration\r\nParameters”:\r\nhttps://www.se.com/ww/en/download/document/31007131K01000/\r\n• Setup a secure communication according to the following guideline\r\n“Modicon Controllers Platform Cyber Security Reference Manual,” in\r\nchapter “Setup secured communications”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 & M580 architectures.\r\nFor more details refer to the chapter “How to protect M580 and M340\r\narchitectures with EAGLE40 using VPN”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Ensure the M340 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline “Modicon Controllers Platform Cyber Security\r\nReference Manual”, “CPU Memory Protection section”:\r\n• https://www.se.com/ww/en/download/document/EIO0000001999/",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/31007131K01000/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n• Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n• Configure the Access Control List following the recommendations of the\r\nuser manuals: “Modicon M580, Hardware, Reference Manual”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\nSetup a secure communication according to the following guideline\r\n“Modicon Controllers Platform Cyber Security Reference Manual,” in\r\nchapter “Setup secured communications”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline “Modicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration\r\nGuide” in the chapter “Configuring IPSEC communications”:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n• Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter “Configuring the\r\nBMENUA0100 Cybersecurity Settings”:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n• Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 & M580 architectures.\r\nFor more details refer to the chapter “How to protect M580 and M340\r\narchitectures with EAGLE40 using VPN”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline “Modicon Controllers Platform Cyber Security\r\nReference Manual”, “CPU Memory Protection section”:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580 Hot\r\nStandby CPUs. In such cases, use IPsec encrypted communication.",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "Schneider Electric is establishing a remediation plan for all future versions\r\nof EcoStruxure™ Process Expert that will include a fix for this vulnerability.\r\nWe will update this document when the remediation is available. Until then,\r\ncustomers should immediately apply the following mitigations to reduce the\r\nrisk of exploit:\r\n• Setup an application password in the project properties\r\n• Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n• Configure the Access Control List following the recommendations of the\r\nuser manuals: “Modicon M580, Hardware, Reference Manual”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\n• Setup a secure communication according to the following guideline\r\n“Modicon Controllers Platform Cyber Security Reference Manual,” in\r\nchapter “Setup secured communications”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline “Modicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration Guide” in the chapter “Configuring IPSEC communications”:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n• Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter “Configuring the\r\nBMENUA0100 Cybersecurity Settings”:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n• Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 & M580 architectures.\r\nFor more details refer to the chapter “How to protect M580 and M340\r\narchitectures with EAGLE40 using VPN”:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n• Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline “Modicon Controllers Platform Cyber Security\r\nReference Manual”, “CPU Memory Protection section”:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580\r\nHot Standby CPUs. In such cases, use IPsec encrypted\r\ncommunication.\r\n• To further reduce the attack surface on Modicon M580 CPU\r\nSafety:\r\nEnsure the CPU is running in Safety mode and maintenance input is\r\nconfigured to maintain this Safety mode during operation – refer to\r\nthe document Modicon M580 - Safety System Planning Guide - in\r\nthe chapter “Operating Mode Transitions”:\r\nhttps://www.se.com/ww/en/download/document/QGH60283/ ",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "Enable encryption on application project and store application files in\r\nsecure location with restricted access only for legitimate users.\r\n• Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n• Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        },
        {
          "category": "mitigation",
          "details": "EcoStruxure Process Expert manages application files within its\r\ndatabase in secure way. Do not export & store them outside the\r\napplication.\r\n• Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n• Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "NONE",
            "baseScore": 7.1,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N",
            "version": "3.1"
          },
          "products": [
            "4",
            "5"
          ]
        }
      ],
      "title": "CVE-2023-27975"
    }
  ]
}